(+86)0532-88988868

How it works: A variable frequency constant pressure water supply system uses the user's water consumption or the network pressure as parameters. It also uses a pressure sensor to monitor the water pressure in the network. The pressure sensor sends the detected signal to the variable frequency drive’s PID loop, and after processing, the output frequency signal adjusts the water pump motor speed. This automatically regulates the network’s water pressure, keeping it consistent with the set pressure value.
When users' water usage increases, the output frequency will rise accordingly, the pump motor will spin faster, and the water supply will increase as well. Conversely, when users' water usage decreases, the output frequency will drop, the pump motor will slow down, and the water supply will decrease accordingly, truly achieving the effect of supplying water according to usage. When multiple pumps are operating, they start up one by one softly, switching from variable frequency to fixed frequency until the pressure and flow requirements are met, enabling circulating control of the pumps. At night, when water demand is low, the frequency converter automatically reduces the output frequency or the pump can shut down to maintain pressure, achieving energy savings.
Applications: water supply for high-rise buildings, residential communities, and offices; industrial process water; city tap water; safe drinking water for towns and rural areas; secondary water supply for urban pipe networks; boiler feed water; water for agriculture and garden irrigation; fire-fighting pressure stabilization; sewage and wastewater treatment; drainage and irrigation systems for large squares and parks, and more.